Applications:
The Dimako earth fault lockout system provides an intrinsically safe search voltage that interrogates system earth isolation, and will lock out circuit devices to prevent energisation onto an earth fault condition. The system is approved to SABS 549 for intrinsic safety.
Display/Indication/Features:
All devices are designed to operate continuously under sustained fault conditions. The unique design allows the system to be permanently connected to the circuit to be monitored (via a false neutral), with very little power dissipation. Led indication is given for trip and healthy conditions.
| Supply | 18Vac -40% + 10% (ex infallible TX) |
| Outputs | 1 normally open contact (Pot free) 1 normally closed contact (Pot free) |
| Connection Detail | Standard 11 pin relay plug |
| Physical Size | Relay – 35mm x 80mm x 75mm False Neutral – 65mm x 80mm x 200m |
| Mounting Detail | The 11 pin base is either omega rail mountable or chassis mountable |